Effluent treatment plants by industry
Effluent treatment plant for hospital
This MBBR effluent treatment plant for hospital is sized at a sample flow of 50 KLD. Plot about 14.7 × 14.2 m (209 m²). Power: 11.2 kW connected, about 88 kWh a day. Computed outlet meets Bio-Medical Waste Management Rules 2016 (liquid waste) for the parameters computed (BOD, COD, TSS, Oil & grease). Not computed here: pH and bio-assay; checked in detailed design. Budget: on request.
Technically reviewed by Prashant Dwivedi, Co-Founder & Director ·
Design summary
| Item | Value |
|---|---|
| Design flow | 50 KLD |
| Flow over running hours | 3.12 m³/h (16 h/day) |
| Flow averaged over 24 h | 2.08 m³/h |
| Technology | MBBR |
| Plot (footprint) | 14.7 × 14.2 m (209 m²) |
| Connected load | 11.2 kW |
| Operating load | 5.9 kW |
| Energy per day | 88 kWh |
| Energy per m³ | 1.75 kWh/m³ |
| Blower air (all duty blowers) | 110 Nm³/h |
| Design method | NBW practice |
Treatment units and sizes
| Unit | Purpose | Volume | Size | Sizing basis |
|---|---|---|---|---|
| Oil and grease trap | removes floating oil and grease | 0.5 m³ | 1.75 × 0.3 × 0.9 m | oil and grease trap at the peak inflow |
| Equalisation tank | stores and evens out the inflow | 25 m³ | 2.65 × 2.7 × 3.5 m | stores the inflow of the 8 h a day the plant does not run, x 1.5 for peaks; air for mixing only, no treatment credit |
| MBBR tank, 2 stages (sieve baffle) | biological treatment: BOD and ammonia removal | 25.5 m³ | 2.7 × 2.7 × 3.5 m | larger of 6 h on the running flow and the tank for the media needed for BOD + ammonia removal; media 10.1 m3 (40 % fill), 2 stages, fine-bubble air |
| Tube settler (hopper bottom) | settles the biological sludge | 9.7 m³ | 1.8 × 1.8 × 3 m | tube settler, surface loading 0.96 m3/m2/h on the running flow, 3.1 h |
| Chlorine contact tank | disinfection (chlorine contact) | 1.6 m³ | 1.15 × 0.4 × 3.5 m | chlorine contact on the running flow |
| Pressure sand filter, FRP 24x72 inch | removes suspended solids | Ø 0.61 m × 1.83 m high | 3.1 m3/h at 10.7 m/h filtration velocity | |
| Activated carbon filter, FRP 36x72 inch | removes colour, odour and chlorine | Ø 0.91 m × 1.83 m high | 3.1 m3/h at 4.8 m/h filtration velocity | |
| Treated water tank | stores the treated water | 16.9 m³ | 2.2 × 2.2 × 3.5 m | treated water storage, about 8 h of average flow |
| Sludge holding tank | holds the excess sludge | 5 m³ | 1.2 × 1.2 × 3.5 m | about 7 days of sludge, air mixed |
| Twin lobe air blower | air for aeration and mixing | 110 Nm3/h at 4.5 m water column, 1 working + 1 standby (serves eq, mbbr, sludge) |
Tank sizes are length × width × depth; vessel sizes are diameter × height.
Water quality, stage by stage
| Stage | BOD | COD | TSS | NH₃-N | Total N | Oil & grease |
|---|---|---|---|---|---|---|
| Inlet | 300 | 600 | 300 | 50 | 50 | 50 |
| Basket screen (inlet chamber) | 300 | 600 | 300 | 50 | 50 | 50 |
| Oil and grease trap | 285 | 571.8 | 300 | 50 | 50 | 20 |
| Equalisation tank | 285 | 571.8 | 300 | 50 | 50 | 20 |
| MBBR bioreactor | 14.3 | 62.8 | 300 | 1 | 39.8 | 4 |
| Tube settler | 12.1 | 58.8 | 30 | 1 | 39.8 | 4 |
| Disinfection | 12.1 | 58.8 | 30 | 1 | 39.8 | 4 |
| Pressure sand filter | 9.1 | 53.1 | 15 | 1 | 39.8 | 4 |
| Activated carbon filter | 5.9 | 34.5 | 15 | 1 | 39.8 | 4 |
| Outlet | 5.9 | 34.5 | 15 | 1 | 39.8 | 4 |
Outlet vs Bio-Medical Waste Management Rules 2016 (liquid waste)
| Parameter | Limit | Computed outlet | Result |
|---|---|---|---|
| BOD | ≤ 30 | 5.9 | Within limit |
| COD | ≤ 250 | 34.5 | Within limit |
| TSS | ≤ 100 | 15 | Within limit |
| Oil & grease | ≤ 10 | 4 | Within limit |
Not computed in this estimate — checked in detailed design:
- pH 6.5-9.0
- bio-assay: 90 % survival of fish after 96 h in 100 % effluent
Design assumptions
- Raw inlet BOD 300 mg/L
- Raw inlet COD 600 mg/L
- Raw inlet TSS 300 mg/L
- Raw inlet TKN 50 mg/L
- Raw inlet oil and grease 50 mg/L
- Raw inlet pH 7.5
- Raw TDS 1,200 mg/L
- Design temperature 15–32 °C
- Checked against: Bio-Medical Waste Management Rules 2016 (liquid waste)
- Plant running 16 hours a day
- Flow basis: about 20-30 % of a hospital's water use
- Discharge assumed: inland surface water (assumed; the consent decides)
- Effluent: laundry, laboratory and kitchen effluent
- Inlet quality: ASSUMED typical values from published ranges for the industry; the plant is designed on the unit's own lab report
- Note: Bio-Medical Waste Rules 2016: disinfection before discharge
Design checks
- screen type: a channel bar screen reaches only 0.14 m/s at a buildable width: basket screen (10 mm) in a 1 x 1 m inlet chamber instead
- alkalinity after nitrification (before dosing): short of alkalinity: NaHCO3 dosed to keep pH >= 6.8
- Activated carbon filter: filtration velocity: smallest standard vessel runs below the velocity range; fine (more contact), or a smaller vessel
Budget
On request. Ask for a budget estimate for your site.
What quotes often exclude
- GST
- Land and civil building / shed
- Site work: excavation, piling, dewatering
- Power connection up to the plant panel
- Consent (CTE / CTO) fees and liaison
- Operation and maintenance after commissioning
Check your SPCB consent
The State Pollution Control Board consent (CTE / CTO) for your project sets the outlet limits the plant must meet, which can be stricter than the national norm. Check it before you finalise the design: STP discharge norms explained.
Frequently asked questions
What size of tanks does a 50 KLD hospital ETP need?
About 84 m3 of tanks in all: oil and grease trap 0.5 m3; equalisation tank 25 m3; mbbr tank 25.5 m3; tube settler (hopper bottom) 9.7 m3; chlorine contact tank 1.6 m3; treated water tank 16.9 m3; sludge holding tank 5 m3.
How much space and power does a 50 KLD hospital ETP need?
A plot about 14.7 x 14.2 m including the equipment room; 11.2 kW connected, 5.9 kW running, about 88 kWh a day (1.75 kWh per m3) at 16 h a day.
Does a 50 KLD hospital ETP meet the BMW Rules 2016 liquid waste standard?
Computed outlet BOD 5.9, TSS 15 mg/L against the BMW Rules 2016 liquid waste standard BOD 30, COD 250, TSS 100 mg/L: within the limits. Its other parameters (pH and those listed on this page) are not computed in this estimate; checked in detailed design.
Related
Preliminary estimate, not for construction. Detailed design and quotation by NBW engineers.
How we calculate: our design method and sources. For a detailed quotation, request a quote.