Tool

STP capacity calculator

STP capacity (KLD) = persons × water supplied per person per day (litres) × sewage factor ÷ 1,000. CPHEEO gives 135 litres per person per day for cities with sewerage and 150 for metro and mega cities; about 80% of that water is commonly taken as sewage. A 100-flat society (500 people) at 135 litres needs about 54 KLD.

Technically reviewed by Prashant Dwivedi, Co-Founder & Director ·

5 is a common planning assumption; use actual occupancy if known.

Common design assumption; CPHEEO notes 40–90%.

Not a CPHEEO rule. Leave at 0 for the book value.

Water demand
67.5 KLD
Sewage flow
54 KLD
With design margin
54 KLD
Hourly flow, 24 h running
2,250 LPH
Hourly flow, 16 h running
3,375 LPH

Working: 100 flats × 5 × 135 × 0.8 ÷ 1000 = 54 KLD

Get a preliminary design for this size

STP capacity for housing societies

5 persons per flat, sewage factor 0.8. Average daily sewage flow before any design margin.
FlatsPersonsKLD at 135 lpcdKLD at 150 lpcd
2512513.515
502502730
1005005460
2001,000108120
5002,500270300

How it is calculated

Sewage flow (KLD) = Occupants × Water supply rate (litres/day) × Sewage factor ÷ 1,000

  1. Count the occupants. Persons = flats × persons per flat (5 is a common planning assumption), or use beds for hospitals and hotels.
  2. Pick the water supply rate. 135 lpcd for cities with sewerage or 150 lpcd for metro and mega cities (CPHEEO 1999 Table 2.1); 340 or 450 l/bed for hospitals, 180 l/bed for hotels, 135 lpcd for hostels (CPHEEO 2013 Table 3.4).
  3. Work out water demand. Water demand (litres per day) = occupants × rate. Divide by 1,000 for KLD.
  4. Apply the sewage factor. Sewage flow = water demand × sewage factor. 0.8 is a common design assumption; CPHEEO 2013 clause 3.5 notes 40–90%.
  5. Convert to hourly flow. Hourly flow (LPH) = KLD × 1,000 ÷ running hours (24 h, or 16 h if the plant runs part of the day).

The optional design margin is Navbharat Water practice for future occupancy and day-to-day variation, not a CPHEEO rule. For the full worked example and peak factors, see how to calculate STP capacity.

Sources

  1. CPHEEO Manual on Water Supply and Treatment, 1999, Table 2.1 (135 / 150 lpcd).
  2. CPHEEO Manual on Sewerage and Sewage Treatment Systems, 2013, clause 3.5 (sewage as 40–90% of water supplied) and Table 3.4 (water demand per bed).

Frequently asked questions

How do I calculate STP capacity for an apartment?

Multiply flats by persons per flat (commonly 5), then by the water supply rate (135 lpcd, or 150 lpcd in metro cities) and by the sewage factor (commonly 0.8), and divide by 1,000. 100 flats give 100 × 5 × 135 × 0.8 ÷ 1,000 = 54 KLD, or 60 KLD at 150 lpcd.

Is the 80% sewage factor a CPHEEO rule?

No. 80% is a common Indian design assumption. The CPHEEO Manual on Sewerage and Sewage Treatment Systems 2013 (clause 3.5) notes the share of water reaching the sewer can range from about 40% in arid areas to 90% in well-developed areas, so the calculator lets you change it.

How is STP capacity worked out for a hospital or hotel?

Use water demand per bed from CPHEEO 2013 Table 3.4: 340 litres per bed per day for hospitals up to 100 beds, 450 above 100 beds, and 180 for hotels. Multiply by beds and the sewage factor, then divide by 1,000. A 150-bed hospital gives 150 × 450 × 0.8 ÷ 1,000 = 54 KLD.

Preliminary estimate, not for construction. Detailed design and quotation by NBW engineers.

How we calculate: our design method and sources.