Effluent treatment plants by industry
Effluent treatment plant for laundry
This physico-chemical + MBBR effluent treatment plant for laundry is sized at a sample flow of 50 KLD. Plot about 16.5 × 16.4 m (271 m²). Power: 11.2 kW connected, about 96 kWh a day. Computed outlet meets EP Rules Sch VI general standards (inland surface water) for the parameters computed (BOD, COD, TSS, Oil & grease). Not computed here: pH, ammoniacal nitrogen, total residual chlorine and 5 more; checked in detailed design. Budget: on request.
Technically reviewed by Prashant Dwivedi, Co-Founder & Director ·
Design summary
| Item | Value |
|---|---|
| Design flow | 50 KLD |
| Flow over running hours | 3.12 m³/h (16 h/day) |
| Flow averaged over 24 h | 2.08 m³/h |
| Technology | physico-chemical + MBBR |
| Plot (footprint) | 16.5 × 16.4 m (271 m²) |
| Connected load | 11.2 kW |
| Operating load | 6.5 kW |
| Energy per day | 96 kWh |
| Energy per m³ | 1.92 kWh/m³ |
| Blower air (all duty blowers) | 83 Nm³/h |
| Design method | NBW practice |
Treatment units and sizes
| Unit | Purpose | Volume | Size | Sizing basis |
|---|---|---|---|---|
| Oil and grease trap | removes floating oil and grease | 0.5 m³ | 1.75 × 0.3 × 0.9 m | oil and grease trap at the peak inflow |
| Equalisation tank | stores and evens out the inflow | 25 m³ | 2.65 × 2.7 × 3.5 m | stores the inflow of the 8 h a day the plant does not run, x 1.5 for peaks; air for mixing only, no treatment credit |
| Neutralisation tank | corrects the pH | 0.6 m³ | 0.8 × 0.8 × 1 m | pH correction to 7.5 |
| Flash mixer | mixes in the coagulant | 0.6 m³ | 0.8 × 0.8 × 1 m | coagulant mixing |
| Flocculator | grows the flocs for settling | 1.1 m³ | 1 × 1.05 × 1.01 m | flocculation with polyelectrolyte |
| Tube settler (hopper bottom) | settles the chemical sludge | 2.8 m³ | 0.95 × 0.95 × 3.1 m | chemical sludge settling by surface loading |
| MBBR tank, 2 stages (sieve baffle) | biological treatment: BOD and ammonia removal | 14 m³ | 2 × 2 × 3.5 m | larger of 6 h on the running flow and the tank for the media needed for BOD + ammonia removal; media 5.5 m3 (39 % fill), 2 stages, fine-bubble air |
| Tube settler (hopper bottom) | settles the biological sludge | 6.3 m³ | 1.45 × 1.45 × 3 m | tube settler, surface loading 0.99 m3/m2/h on the running flow, 3.0 h |
| Chlorine contact tank | disinfection (chlorine contact) | 1.1 m³ | 0.9 × 0.35 × 3.5 m | chlorine contact on the running flow |
| Pressure sand filter, FRP 21x62 inch | removes suspended solids | Ø 0.53 m × 1.57 m high | 2.1 m3/h at 9.3 m/h filtration velocity | |
| Activated carbon filter, FRP 30x72 inch | removes colour, odour and chlorine | Ø 0.76 m × 1.83 m high | 2.1 m3/h at 4.6 m/h filtration velocity | |
| Treated water tank | stores the treated water | 16.9 m³ | 2.2 × 2.2 × 3.5 m | treated water storage, about 8 h of average flow |
| Sludge holding tank | holds the excess sludge | 12 m³ | 1.85 × 1.85 × 3.5 m | about 7 days of sludge, air mixed |
| Filter press, 470 x 470 mm, 17 chambers | dewaters the sludge to cake | 470 mm plates, 17 chambers, 74 kg/d wet cake | ||
| Twin lobe air blower | air for aeration and mixing | 83 Nm3/h at 4.5 m water column, 1 working + 1 standby (serves eq, mbbr, sludge) |
Tank sizes are length × width × depth; vessel sizes are diameter × height.
Water quality, stage by stage
| Stage | BOD | COD | TSS | NH₃-N | Total N | Oil & grease |
|---|---|---|---|---|---|---|
| Inlet | 300 | 800 | 250 | 10 | 10 | 50 |
| Basket screen (inlet chamber) | 300 | 800 | 250 | 10 | 10 | 50 |
| Oil and grease trap | 285 | 762.4 | 250 | 10 | 10 | 20 |
| Equalisation tank | 285 | 762.4 | 250 | 10 | 10 | 20 |
| Neutralisation tank | 285 | 762.4 | 250 | 10 | 10 | 20 |
| Flash mixer | 285 | 762.4 | 250 | 10 | 10 | 20 |
| Flocculator | 285 | 762.4 | 250 | 10 | 10 | 20 |
| Tube settler (chemical sludge) | 285 | 762.4 | 100 | 10 | 10 | 20 |
| MBBR bioreactor | 14.3 | 83.7 | 100 | 1 | 1 | 4 |
| Tube settler | 12.1 | 78.4 | 30 | 1 | 1 | 4 |
| Disinfection | 12.1 | 78.4 | 30 | 1 | 1 | 4 |
| Pressure sand filter | 9.1 | 70.8 | 15 | 1 | 1 | 4 |
| Activated carbon filter | 5.9 | 46 | 15 | 1 | 1 | 4 |
| Outlet | 5.9 | 46 | 15 | 1 | 1 | 4 |
Outlet vs EP Rules Sch VI general standards (inland surface water)
| Parameter | Limit | Computed outlet | Result |
|---|---|---|---|
| BOD | ≤ 30 | 5.9 | Within limit |
| COD | ≤ 250 | 46 | Within limit |
| TSS | ≤ 100 | 15 | Within limit |
| Oil & grease | ≤ 10 | 4 | Within limit |
Not computed in this estimate — checked in detailed design:
- pH 5.5-9.0
- ammoniacal nitrogen 50 mg/L
- total residual chlorine 1.0 mg/L
- dissolved phosphates (as P) 5.0 mg/L
- sulphide 2.0 mg/L
- phenolic compounds 1.0 mg/L
- bio-assay: 90 % survival of fish after 96 h in 100 % effluent
- heavy metals (EP Rules Sch. VI Part A)
Design assumptions
- Raw inlet BOD 300 mg/L
- Raw inlet COD 800 mg/L
- Raw inlet TSS 250 mg/L
- Raw inlet TKN 10 mg/L
- Raw inlet oil and grease 50 mg/L
- Raw inlet pH 9.5
- Raw TDS 1,500 mg/L
- Design temperature 15–32 °C
- Checked against: EP Rules Sch VI general standards (inland surface water)
- Plant running 16 hours a day
- Flow basis: about 15-25 L per kg of linen
- Discharge assumed: inland surface water (assumed; the consent decides)
- Inlet quality: ASSUMED typical values from published ranges for the industry; the plant is designed on the unit's own lab report
- Note: detergent and lint; pH correction
Design checks
- screen type: a channel bar screen reaches only 0.14 m/s at a buildable width: basket screen (10 mm) in a 1 x 1 m inlet chamber instead
- Activated carbon filter: filtration velocity: smallest standard vessel runs below the velocity range; fine (more contact), or a smaller vessel
Engineering notes
Points our engineers confirm during detailed design:
- alkalinity titrated: pH alone misses the carbonate / buffer alkalinity: the acid dose is a lower bound until the alkalinity is titrated
Budget
On request. Ask for a budget estimate for your site.
What quotes often exclude
- GST
- Land and civil building / shed
- Site work: excavation, piling, dewatering
- Power connection up to the plant panel
- Consent (CTE / CTO) fees and liaison
- Operation and maintenance after commissioning
Check your SPCB consent
The State Pollution Control Board consent (CTE / CTO) for your project sets the outlet limits the plant must meet, which can be stricter than the national norm. Check it before you finalise the design: STP discharge norms explained.
Frequently asked questions
What size of tanks does a 50 KLD laundry ETP need?
About 81 m3 of tanks in all: oil and grease trap 0.5 m3; equalisation tank 25 m3; neutralisation tank 0.6 m3; flash mixer 0.6 m3; flocculator 1.1 m3; tube settler (hopper bottom) 2.8 m3; mbbr tank 14 m3; tube settler (hopper bottom) 6.3 m3; chlorine contact tank 1.1 m3; treated water tank 16.9 m3; sludge holding tank 12 m3.
How much space and power does a 50 KLD laundry ETP need?
A plot about 16.5 x 16.4 m including the equipment room; 11.2 kW connected, 6.5 kW running, about 96 kWh a day (1.92 kWh per m3) at 16 h a day.
Does a 50 KLD laundry ETP meet MoEF inland surface water?
Computed outlet BOD 5.9, TSS 15 mg/L against MoEF inland surface water BOD 30, COD 250, TSS 100 mg/L: within the limits. Its other parameters (pH and those listed on this page) are not computed in this estimate; checked in detailed design.
Related
Preliminary estimate, not for construction. Detailed design and quotation by NBW engineers.
How we calculate: our design method and sources. For a detailed quotation, request a quote.