Skip to main content

RO plants by capacity

500 LPH industrial RO plant: sizing, power and running cost

A 500 LPH RO plant at 70 % recovery takes about 750 L/h of feed water and rejects 230 L/h. It uses 4 x 4 inch membranes and a 0.6 kW high-pressure pump. Plot about 9.4 × 10.2 m (96 m²). Power: 2.4 kW connected, about 15 kWh a day. Computed outlet meets IS 10500:2012 for the parameters computed (TDS). Budget: ₹1.5 L – ₹3.5 L (typical market range, not an NBW quotation).

Technically reviewed by Prashant Dwivedi, Co-Founder & Director ·

Design summary

ItemValue
Design flow8 KLD
Flow over running hours0.5 m³/h (16 h/day)
Flow averaged over 24 h0.33 m³/h
Plot (footprint)9.4 × 10.2 m (96 m²)
Connected load2.4 kW
Operating load1 kW
Energy per day15 kWh
Energy per m³1.93 kWh/m³
Design methodNBW practice

RO design

ItemValue
Product water500 L/h
Recovery70 %
Feed water750 L/h
Reject230 L/h
Membranes4 x 4 inch
High-pressure pump0.6 kW
PretreatmentMultimedia filter; RO feed dosing (SMBS, acid, antiscalant); Cartridge filter, 5 micron

Treatment units and sizes

UnitPurposeVolumeSizeSizing basis
Raw water tank (client's scope, existing)raw water storage2 m³Ø 1.29 m × 1.53 m highexisting tank, client's scope
Multimedia filter, FRP 12x52 inchremoves turbidity and suspended solidsØ 0.3 m × 1.32 m high0.8 m3/h at 11.1 m/h filtration velocity
Cartridge filter, 5 micron: 1 x 20 inch elementsprotects the membranes (5 micron)Ø 0.27 m × 0.86 m high1 x 20 inch, 5 micron elements
RO skidremoves dissolved salts (reverse osmosis)4 x 4 inch elements in 1 pressure vessel(s), array 1, flux 17.3 L/m2/h, recovery 70%
Product (treated) water tankstores the treated water0.5 m³Ø 0.81 m × 0.97 m highHDPE tank

Tank sizes are length × width × depth; vessel sizes are diameter × height.

Water quality, stage by stage

mg/L, computed, compared with IS 10500:2012.
StageTDSMeets norm
Raw water1,500No
RO permeate55.7Yes
Outlet55.7Yes
Norm limit (IS 10500:2012)≤ 500

Design assumptions

  • Raw water TDS 1,500 mg/L
  • Raw water total hardness 450 mg/L as CaCO₃
  • Checked against: IS 10500:2012
  • Plant running 16 hours a day
  • Raw water: ASSUMED typical hard borewell water; the plant is designed on the site's lab report

Design checks

  • typical borewell: SIO2 not measured: needed for the membrane projection
  • typical borewell: BA not measured: needed for the membrane projection
  • typical borewell: SR not measured: needed for the membrane projection
  • typical borewell: K not measured: needed for the membrane projection

Engineering notes

Points our engineers confirm during detailed design:

  • Specific energy is above the usual RO range at this small size (fixed panel, dosing and instrument load on a small output, smallest standard pumps); pump duty is optimised in detailed design

Budget

Typical market range (published figures, 2026) — not an NBW quotation

CAPEX, turnkey plant. ±30%. Excludes GST, land, civil building and site work.
CapacityRO — raw/process water
10 KLD₹1.5 L – ₹3.5 L
Running cost (O&M) per KL treated: power, chemicals, manpower, sludge and AMC/membranes. Typical market range (published figures, 2026) — not an NBW quotation.
CapacityRO — raw/process water
10 KLD₹25 – 45 per KL

These are published market figures, not Navbharat Water's prices. For our own estimate for your project, request a quote.

What quotes often exclude

  • GST
  • Land and civil building / shed
  • Site work: excavation, piling, dewatering
  • Power connection up to the plant panel
  • Consent (CTE / CTO) fees and liaison
  • Operation and maintenance after commissioning

Frequently asked questions

What does a 500 LPH RO plant need?

4 x 4 inch membranes (array 1), feed 750 L/h, reject 230 L/h at 70 % recovery; pretreatment: multimedia filter, ro feed dosing (smbs, acid, antiscalant), cartridge filter, 5 micron.

How much space and power does a 500 LPH RO plant need?

A plot about 9.4 x 10.2 m including the equipment room; 2.4 kW connected, 1 kW running, about 15 kWh a day (1.93 kWh per m3) at 16 h a day.

Does a 500 LPH RO plant meet IS 10500:2012?

Computed outlet TDS 55.7 mg/L against IS 10500:2012 TDS 500 mg/L: within the limits.

Related

Preliminary estimate, not for construction. Detailed design and quotation by NBW engineers.

How we calculate: our design method and sources. For a detailed quotation, request a quote.