Skip to main content

Water softener plants

Water softener plant for a 100-flat housing society

A softener for 100 flats treating 4,220 L/h over 16 h a day. It needs 825 L of resin per vessel, 1 regeneration(s) a day, 124 kg salt per regeneration. Plot about 6 × 9.2 m (55 m²). Power: 1.1 kW connected, about 1 kWh a day. Budget: on request.

Technically reviewed by Prashant Dwivedi, Co-Founder & Director ·

Design summary

ItemValue
Flow over running hours4.22 m³/h (16 h/day)
Flow averaged over 24 h2.81 m³/h
Flats100
Plot (footprint)6 × 9.2 m (55 m²)
Connected load1.1 kW
Operating load0.9 kW
Energy per day1 kWh
Energy per m³0.01 kWh/m³
Softener vessels1 working + 1 regenerating, 36x72 FRP
Resin per vessel825 L
Salt per regeneration124 kg
Regenerations per day1
Design methodNBW practice

Treatment units and sizes

UnitPurposeVolumeSizeSizing basis
Softener, FRP 36x72 inch (+ 1 regenerating)removes hardness (resin softening)Ø 0.91 m × 1.83 m highvessel by area at the service velocity; 0.825 m3 resin per vessel, 1 regenerations a day
Brine tank with salt gridbrine for regeneration3 m³Ø 1.47 m × 1.77 m highHDPE tank

Tank sizes are length × width × depth; vessel sizes are diameter × height.

Water quality, stage by stage

mg/L, computed, compared with IS 10500:2012.
StageHardness
Raw water500
Soft water5

Design assumptions

  • Raw TDS 900 mg/L
  • Raw water hardness 500 mg/L as CaCO₃
  • Checked against: IS 10500:2012
  • Plant running 16 hours a day
  • Flow basis: 100 flats x 5 persons x 135 L/person/day over 16 h
  • Raw water: ASSUMED hard borewell water

Budget

On request. Ask for a budget estimate for your site.

What quotes often exclude

  • GST
  • Land and civil building / shed
  • Site work: excavation, piling, dewatering
  • Power connection up to the plant panel
  • Consent (CTE / CTO) fees and liaison
  • Operation and maintenance after commissioning

Frequently asked questions

How much resin does a water softener for 100 flats need?

825 L per vessel in 36x72 FRP vessels (1 working + 1 regenerating), 1 regeneration(s) a day, 124 kg salt per regeneration.

How much space and power does a Water softener for 100 flats need?

A plot about 6 x 9.2 m including the equipment room; 1.1 kW connected, 0.9 kW running, about 0.8 kWh a day (0.011 kWh per m3) at 16 h a day.

Related

Preliminary estimate, not for construction. Detailed design and quotation by NBW engineers.

How we calculate: our design method and sources. For a detailed quotation, request a quote.