Industrial water softener: sizing by flow and hardness
A softener treating 5,000 L/h over 16 h a day. It needs 600 L of resin per vessel, 1 regeneration(s) a day, 90 kg salt per regeneration. Plot about 6 × 9 m (54 m²). Power: 1.1 kW connected, about 1 kWh a day. Budget: on request.
Technically reviewed by Prashant Dwivedi, Co-Founder & Director ·
Design summary
| Item | Value |
|---|---|
| Flow over running hours | 5 m³/h (16 h/day) |
| Flow averaged over 24 h | 3.33 m³/h |
| Plot (footprint) | 6 × 9 m (54 m²) |
| Connected load | 1.1 kW |
| Operating load | 0.9 kW |
| Energy per day | 1 kWh |
| Energy per m³ | 0.01 kWh/m³ |
| Softener vessels | 1 working + 1 regenerating, 36x72 FRP |
| Resin per vessel | 600 L |
| Salt per regeneration | 90 kg |
| Regenerations per day | 1 |
| Design method | NBW practice |
Treatment units and sizes
| Unit | Purpose | Volume | Size | Sizing basis |
|---|---|---|---|---|
| Softener, FRP 36x72 inch (+ 1 regenerating) | removes hardness (resin softening) | Ø 0.91 m × 1.83 m high | vessel by area at the service velocity; 0.6 m3 resin per vessel, 1 regenerations a day | |
| Brine tank with salt grid | brine for regeneration | 2 m³ | Ø 1.29 m × 1.53 m high | HDPE tank |
Tank sizes are length × width × depth; vessel sizes are diameter × height.
Water quality, stage by stage
| Stage | Hardness |
|---|---|
| Raw water | 300 |
| Soft water | 5 |
Design assumptions
- Raw TDS 700 mg/L
- Raw water hardness 300 mg/L as CaCO₃
- Checked against: IS 10500:2012
- Plant running 16 hours a day
- Flow basis: given flow
- Raw water: ASSUMED hard borewell water
Budget
On request. Ask for a budget estimate for your site.
What quotes often exclude
- GST
- Land and civil building / shed
- Site work: excavation, piling, dewatering
- Power connection up to the plant panel
- Consent (CTE / CTO) fees and liaison
- Operation and maintenance after commissioning
Frequently asked questions
How much resin does a water softener, 5 m3/h need?
600 L per vessel in 36x72 FRP vessels (1 working + 1 regenerating), 1 regeneration(s) a day, 90 kg salt per regeneration.
How much space and power does a Water softener, 5 m3/h need?
A plot about 6 x 9 m including the equipment room; 1.1 kW connected, 0.9 kW running, about 0.5 kWh a day (0.007 kWh per m3) at 16 h a day.
Related
Preliminary estimate, not for construction. Detailed design and quotation by NBW engineers.
How we calculate: our design method and sources. For a detailed quotation, request a quote.