A 300-flat society (about 1,500 people) needs a 165 KLD MBBR STP (162 KLD computed, rounded up to 165 KLD design flow). Plot about 21 × 18.9 m (397 m²). Power: 29.2 kW connected, about 238 kWh a day. Computed outlet meets NGT 2019 (O.A. 1069/2018) for the parameters computed (BOD, COD, TSS, Total N). Budget: ₹46 L – ₹76 L (typical market range, not an NBW quotation).

Technically reviewed by Prashant Dwivedi, Co-Founder & Director ·

Design summary

ItemValue
Design flow165 KLD
Flow over running hours10.31 m³/h (16 h/day)
Flow averaged over 24 h6.88 m³/h
TechnologyMBBR
Flats300
Persons1,500
Plot (footprint)21 × 18.9 m (397 m²)
Connected load29.2 kW
Operating load15.3 kW
Energy per day238 kWh
Energy per m³1.44 kWh/m³
Blower air (all duty blowers)301 Nm³/h
Design methodNBW practice

Treatment units and sizes

UnitPurposeVolumeSizeSizing basis
Equalisation tankstores and evens out the inflow83.2 m³4.85 × 4.9 × 3.5 mstores the inflow of the 8 h a day the plant does not run, x 1.5 for peaks; air for mixing only, no treatment credit
MBBR anoxic tankremoves nitrate (denitrification)10.4 m³1.7 × 1.75 × 3.5 manoxic (denitrification), 1 h on the running flow; nitrate recycle 3 x
MBBR tank, 2 stages (sieve baffle)biological treatment: BOD and ammonia removal70.1 m³4.45 × 4.5 × 3.5 mlarger of 6 h on the running flow and the tank for the media needed for BOD + ammonia removal; media 27.8 m3 (40 % fill), 2 stages, fine-bubble air
Secondary clarifier (hopper bottom)settles the biological sludge62.1 m³4.55 × 4.55 × 3 mclarifier by surface loading, 6.0 h
Chlorine contact tankdisinfection (chlorine contact)5.2 m³2 × 0.75 × 3.5 mchlorine contact on the running flow
Pressure sand filter, MS 1100 mm, 4 mm FRP linedremoves suspended solidsØ 1.1 m × 1.8 m high10.3 m3/h at 10.8 m/h filtration velocity
Activated carbon filter, MS 1500 mm, 4 mm FRP linedremoves colour, odour and chlorineØ 1.5 m × 1.8 m high10.3 m3/h at 5.8 m/h filtration velocity
Treated water tankstores the treated water55.3 m³3.95 × 4 × 3.5 mtreated water storage, about 8 h of average flow
Sludge holding tankholds the excess sludge14.7 m³2.05 × 2.05 × 3.5 mabout 7 days of sludge, air mixed
Twin lobe air blowerair for aeration and mixing301 Nm3/h at 4.5 m water column, 1 working + 1 standby (serves eq, mbbr, sludge)

Tank sizes are length × width × depth; vessel sizes are diameter × height.

Water quality, stage by stage

mg/L, computed.
StageBODCODTSSNH₃-NTotal NOil & grease
Inlet250500250404030
Basket screen (inlet chamber)250500250404030
Grit chamber250500250404030
Equalisation tank250500250404030
MBBR anoxic tank159.7330.32504017.430
MBBR bioreactor84525018.56
Secondary clarifier6.842.83018.56
Disinfection6.842.83018.56
Pressure sand filter5.139.61518.56
Activated carbon filter3.325.71518.56
Outlet3.325.71518.56

Outlet vs NGT 2019 (O.A. 1069/2018)

NGT order 30-04-2019 (STPs). Source: Order dated 30-04-2019, para on STP standards. mg/L.
ParameterLimitComputed outletResult
BOD≤ 103.3Within limit
COD≤ 5025.7Within limit
TSS≤ 2015Within limit
Total N≤ 108.5Within limit

Design assumptions

  • Raw inlet BOD 250 mg/L
  • Raw inlet COD 500 mg/L
  • Raw inlet TSS 250 mg/L
  • Raw inlet TKN 40 mg/L
  • Raw inlet oil and grease 30 mg/L
  • Design temperature 15–32 °C
  • Checked against: NGT 2019 (O.A. 1069/2018)
  • Plant running 16 hours a day
  • Flow basis: 300 flats x 5 persons x 135 L/person/day water x 0.8 to sewer = 162.0 KLD, plant 165 KLD
  • Design flow rule: design flow = computed sewage flow rounded up to the next 5 KLD (minimum 10 KLD)
  • Water use: water supply 135 L/person/day (CPHEEO Manual on Water Supply and Treatment 1999)
  • Sewage: sewage = 80 % of water supplied (common design assumption; CPHEEO 2013 cl. 3.5 gives 40-90 %)
  • Inlet quality: typical domestic sewage (CPHEEO 2013), no lab report; COD = 2 x BOD

Design checks

  • screen type: a channel bar screen reaches only 0.57 m/s at a buildable width: basket screen (10 mm) in a 1 x 1 m inlet chamber instead
  • alkalinity after nitrification (before dosing): short of alkalinity: NaHCO3 dosed to keep pH >= 6.8

Budget

Typical market range (published figures, 2026) — not an NBW quotation

CAPEX, turnkey plant. ±30%. Excludes GST, land, civil building and site work.
CapacitySTP — MBBR
165 KLD₹46 L – ₹76 L
Running cost (O&M) per KL treated: power, chemicals, manpower, sludge and AMC/membranes. Typical market range (published figures, 2026) — not an NBW quotation.
CapacitySTP — MBBR
165 KLD₹9 – 17 per KL

These are published market figures, not Navbharat Water's prices. For our own estimate for your project, request a quote.

What quotes often exclude

  • GST
  • Land and civil building / shed
  • Site work: excavation, piling, dewatering
  • Power connection up to the plant panel
  • Consent (CTE / CTO) fees and liaison
  • Operation and maintenance after commissioning

Check your SPCB consent

The State Pollution Control Board consent (CTE / CTO) for your project sets the outlet limits the plant must meet, which can be stricter than the national norm. Check it before you finalise the design: STP discharge norms explained.

Frequently asked questions

What size of tanks does a STP for 300 flats (165 KLD) need?

About 301 m3 of tanks in all: equalisation tank 83.2 m3; mbbr anoxic tank 10.4 m3; mbbr tank 70.1 m3; secondary clarifier (hopper bottom) 62.1 m3; chlorine contact tank 5.2 m3; treated water tank 55.3 m3; sludge holding tank 14.7 m3.

How much space and power does a STP for 300 flats (165 KLD) need?

A plot about 21 x 18.9 m including the equipment room; 29.2 kW connected, 15.3 kW running, about 238 kWh a day (1.44 kWh per m3) at 16 h a day.

Does a STP for 300 flats (165 KLD) meet NGT 2019?

Computed outlet BOD 3.3, TSS 15 mg/L against NGT 2019 BOD 10, COD 50, TSS 20 mg/L: within the limits.

Related

Preliminary estimate, not for construction. Detailed design and quotation by NBW engineers.