Sewage treatment plants by capacity
50 KLD MBR sewage treatment plant: sizes, footprint, power and budget
This 50 KLD MBR sewage treatment plant is sized for 16 hours of running a day. Plot about 12.9 × 14.1 m (182 m²). Power: 15.2 kW connected, about 125 kWh a day. Computed outlet meets NGT 2019 (O.A. 1069/2018) for the parameters computed (BOD, COD, TSS, Total N). Budget: ₹35 L – ₹50 L (typical market range, not an NBW quotation).
Technically reviewed by Prashant Dwivedi, Co-Founder & Director ·
Design summary
| Item | Value |
|---|---|
| Design flow | 50 KLD |
| Flow over running hours | 3.12 m³/h (16 h/day) |
| Flow averaged over 24 h | 2.08 m³/h |
| Technology | MBR |
| Plot (footprint) | 12.9 × 14.1 m (182 m²) |
| Connected load | 15.2 kW |
| Operating load | 8.2 kW |
| Energy per day | 125 kWh |
| Energy per m³ | 2.5 kWh/m³ |
| Blower air (all duty blowers) | 183 Nm³/h |
| Design method | NBW practice |
Treatment units and sizes
| Unit | Purpose | Volume | Size | Sizing basis |
|---|---|---|---|---|
| Oil and grease trap | removes floating oil and grease | 0.7 m³ | 2.6 × 0.3 × 0.9 m | oil and grease trap at the peak inflow |
| Equalisation tank | stores and evens out the inflow | 25 m³ | 2.65 × 2.7 × 3.5 m | stores the inflow of the 8 h a day the plant does not run, x 1.5 for peaks; air for mixing only, no treatment credit |
| MBR aerobic / membrane tank (flat sheet) | biological treatment and membrane filtration | 12.6 m³ | 1.9 × 1.9 × 3.5 m | membrane tank: 160 m2 flat-sheet membrane, net flux 19.5 L/m2/h, 4.0 h aerobic |
| MBR anoxic tank | removes nitrate (denitrification) | 3.2 m³ | 0.95 × 0.95 × 3.5 m | anoxic (denitrification) on the running flow |
| Chlorine contact tank | disinfection (chlorine contact) | 1.6 m³ | 1.15 × 0.4 × 3.5 m | chlorine contact on the running flow |
| Treated water tank | stores the treated water | 16.9 m³ | 2.2 × 2.2 × 3.5 m | treated water storage, about 8 h of average flow |
| Sludge holding tank | holds the excess sludge | 4.4 m³ | 1.1 × 1.15 × 3.5 m | about 7 days of sludge, air mixed |
| Twin lobe air blower | air for aeration and mixing | 183 Nm3/h at 4.5 m water column, 1 working + 1 standby (serves eq, mbr, mbr, sludge) |
Tank sizes are length × width × depth; vessel sizes are diameter × height.
Water quality, stage by stage
| Stage | BOD | COD | TSS | NH₃-N | Total N | Oil & grease |
|---|---|---|---|---|---|---|
| Inlet | 250 | 500 | 250 | 40 | 40 | 30 |
| Basket screen (inlet chamber) | 250 | 500 | 250 | 40 | 40 | 30 |
| Oil and grease trap | 237.5 | 476.5 | 250 | 40 | 40 | 12 |
| Equalisation tank | 237.5 | 476.5 | 250 | 40 | 40 | 12 |
| Membrane bioreactor (MBR) | 4.8 | 38.9 | 2 | 1 | 8 | 2.4 |
| Disinfection | 4.8 | 38.9 | 2 | 1 | 8 | 2.4 |
| Outlet | 4.8 | 38.9 | 2 | 1 | 8 | 2.4 |
Outlet vs NGT 2019 (O.A. 1069/2018)
| Parameter | Limit | Computed outlet | Result |
|---|---|---|---|
| BOD | ≤ 10 | 4.8 | Within limit |
| COD | ≤ 50 | 38.9 | Within limit |
| TSS | ≤ 20 | 2 | Within limit |
| Total N | ≤ 10 | 8 | Within limit |
Design assumptions
- Raw inlet BOD 250 mg/L
- Raw inlet COD 500 mg/L
- Raw inlet TSS 250 mg/L
- Raw inlet TKN 40 mg/L
- Raw inlet oil and grease 30 mg/L
- Design temperature 15–32 °C
- Checked against: NGT 2019 (O.A. 1069/2018)
- Plant running 16 hours a day
- Inlet quality: typical domestic sewage (CPHEEO 2013), no lab report; COD = 2 x BOD
Design checks
- screen type: a channel bar screen reaches only 0.21 m/s at a buildable width: basket screen (10 mm) in a 1 x 1 m inlet chamber instead
Engineering notes
Points our engineers confirm during detailed design:
- SADp (scour air per permeate): 30.7 is outside ..30 Nm3/m3
Budget
Typical market range (published figures, 2026) — not an NBW quotation
| Capacity | STP — MBR |
|---|---|
| 50 KLD | ₹35 L – ₹50 L |
| Capacity | STP — MBR |
|---|---|
| 50 KLD | ₹22 – 38 per KL |
These are published market figures, not Navbharat Water's prices. For our own estimate for your project, request a quote.
What quotes often exclude
- GST
- Land and civil building / shed
- Site work: excavation, piling, dewatering
- Power connection up to the plant panel
- Consent (CTE / CTO) fees and liaison
- Operation and maintenance after commissioning
Check your SPCB consent
The State Pollution Control Board consent (CTE / CTO) for your project sets the outlet limits the plant must meet, which can be stricter than the national norm. Check it before you finalise the design: STP discharge norms explained.
Frequently asked questions
What size of tanks does a 50 KLD MBR STP need?
About 64 m3 of tanks in all: oil and grease trap 0.7 m3; equalisation tank 25 m3; mbr aerobic / membrane tank (flat sheet) 12.6 m3; mbr anoxic tank 3.2 m3; chlorine contact tank 1.6 m3; treated water tank 16.9 m3; sludge holding tank 4.4 m3.
How much space and power does a 50 KLD MBR STP need?
A plot about 12.9 x 14.1 m including the equipment room; 15.2 kW connected, 8.2 kW running, about 125 kWh a day (2.5 kWh per m3) at 16 h a day.
Does a 50 KLD MBR STP meet NGT 2019?
Computed outlet BOD 4.8, TSS 2 mg/L against NGT 2019 BOD 10, COD 50, TSS 20 mg/L: within the limits.
Related
- STP cost per KLD in India
- STP capacity calculator
- How to calculate STP capacity
- MBBR vs SBR vs MBR
- What KLD means (KLD to LPH)
Preliminary estimate, not for construction. Detailed design and quotation by NBW engineers.